Temperature range | fixed -50°C …+180°C
flexing -20°C …+150°C |
Bending radius min. | fixed min. 4 x D
flexing min. 8 x D |
Conductor resistance | 0.75 mm² max. 26.0 Ω/km
1.0 mm² max. 19.5 Ω/km 1.5 mm² max. 13.3 Ω/km 2.5 mm² max. 7.98 Ω/km |
Insulation resistance min. | min. 20 MΩ x km |
Test voltage | 2000 V |
Operating voltage max. | max. 300/500 V |
Standards | EN 50525-2-83 |
Fire performance | Vertical flame propagation EN 60332-1-2
Vertical flame propagation EN 60332-3-24 “Category C” Corrosive gas EN 60754-1/2 Smoke density EN 61034-2 Continuity of flow IEC 60331-21 FE180 |
EU declaration of conformity | LVD Low Voltage Directive 2014/35/EU
RoHS Restriction of Hazardous Substances 2011/65/EU |
The cable with silicone insulation and sheath is used in dry or wet interior areas with high ambient temperature not exposed to mechanical strain. Offers practical advantages thanks to flexible design. Primarily used as a power cable in heating coils and furnaces as well as foundries, glass & ceramic workshops and engineering projects for measuring, controlling and power supplying purposes.
Conductor Stranded copper wire Class 5, IEC 60228
Insulation Silicone insulation, in compliance with HD 308 S2 insulation colour coding EI2 EN 50363-1
Sheath Silicone, RAL 2003 Tile Red EM9 EN 50363-2-1