J-Y(St)Y…Lg

Category:
Temperature range -30°C …+70°C
Bending radius min. min. 10 x D
Loop resistance Ø 0.60 mm max. 130 Ω/km

Ø 0.80 mm max. 73.2 Ω/km

Ø 1.0 mm max. 44.4 Ω/km

1.0 mm² max. 36.2 Ω/km

1.5 mm² max. 24.2 Ω/km

2.5 mm² max. 14.8 Ω/km

Capacitance

Capacity imbalance

max. 100 nF/km

max. 300 pF/100 m

Insulation resistance min. min. 100 MΩ x km
Test voltage 800 Vac core/core

800 Vac core/screen

Operating voltage max. Max 300 V
Standards TSE K 173, DIN VDE 0815
Fire performance Vertical flame propagation EN 60332-1-2
EU declaration of conformity LVD Low Voltage Directive 2014/35/EU

RoHS Restriction of Hazardous Substances 2011/65/EU

PVC insulated and sheathed cable range is used for signal and data transmission in fixed interior installations in dry or wet areas. The cable is protected against ambient electromagnetic interference by its static screen. Used between the control panel and detectors, buttons and field control modules in the fire alarm system.

Conductor Electrolytic copper wire Insulation PVC, in compliance with DIN VDE 0815

insulation colour coding TI51 EN 50290-2-21, YI1 DIN VDE 0207-4 Screen Pet tape min. 100% coverage Tinned copper drain wire Al-Pet tape min. 100% coverage Al-Pet tape min. 100% coverage

Sheath PVC, RAL 3000 Red TM51 EN 50290-2-22, YM1 DIN VDE 0207-5