Temperature range | -30°C …+70°C |
Bending radius min. | min. 10 x D |
Loop resistance | Ø 0.60 mm max. 130 Ω/km
Ø 0.80 mm max. 73.2 Ω/km Ø 1.0 mm max. 44.4 Ω/km 1.0 mm² max. 36.2 Ω/km 1.5 mm² max. 24.2 Ω/km 2.5 mm² max. 14.8 Ω/km |
Capacitance
Capacity imbalance |
100 nF/km
max. 300 pF/100 m |
Insulation resistance min. | min. 100 MΩ x km |
Test voltage | 800 Vac core/core
800 Vac core/screen |
Operating voltage max. | Max 300 V |
Standards | TSE K 173, DIN VDE 0815 |
Fire performance | Vertical flame propagation EN 60332-1-2
Corrosive gas EN 60754-1/2 Smoke density EN 61034-2 |
EU declaration of conformity | LVD Low Voltage Directive 2014/35/EU
RoHS Restriction of Hazardous Substances 2011/65/EU |
Halogen Free insulated and sheathed cable range is used for signal and data transmission in fixed interior installations in dry or wet areas. The cable is protected against ambient electromagnetic interference by its static screen. Used between the control panel and detectors, buttons and field control modules in the fire alarm system. Cables are composed of halogen-free materials (flame retardant materials that do not emit toxic gas or black dense smoke that lowers visibility). They are primarily used in highly populated areas that should have fire resistance.
Conductor Electrolytic copper wire Insulation HFFR, in compliance with DIN VDE 0815
insulation colour coding 70°C EN 50290-2-26, HJ2 DIN VDE 0207-23 Screen Pet tape min. 100% coverage Tinned copper drain wire Al-Pet tape min. 100% coverage
Sheath HFFR, RAL 3000 Red 70°C EN 50290-2-27, HM2 DIN VDE 0207-24