Temperature range | fixed -30°C …+70°C flexing 0°C …+50°C |
Bending radius min. | fixed min. 7.5 x D
flexing min. 15 x D |
Oil resistance | EN 60811-404 |
Conductor resistance | 0.50 mm² max. 39.0 Ω/km 0.75 mm² max. 26.0 Ω/km 1.0 mm² max. 19.5 Ω/km 1.5 mm² max. 13.3 Ω/km 2.5 mm² max. 7.98 Ω/km |
Insulation resistance min. | 20 MΩ x km |
Test voltage | 2500 V |
Operating voltage max. | 300/500 V |
Standards | EN 50525-2-51 |
Fire performance | Vertical flame propagation EN 60332-1-2 |
EU declaration of conformity | LVD Low Voltage Directive 2014/35/EU RoHS Restriction of Hazardous Substances 2011/65/EU |
It is an oil-resistant flexible PVC insulated and sheathed control cable with number-coded cores, braided, tinned copper screen. Used in dry or wet interior areas not exposed to mechanical strain. Preferred for mobile installations and confined spaces thanks to its flexible design. Used for measurement and control functions in electronic control systems, production and assembly lines and engineering projects. NYSLYCYÖ-OZ: black core with white number codes NYSLYCYÖJZ: ground protection conductor (yellow/green), black core with white number codes
Conductor Stranded copper wire Class 5, IEC 60228
Insulation PVC, in compliance with EN 50334 insulation colour coding, black core with white number codes TI2 EN 50363-3
Inner Sheath PVC TM2 EN 50363-4-1
Screen Braided screen made of tinned copper wires
Sheath PVC – RAL 7001 Grey TM5 EN 50363-4-1