Temperature range | 20°C …+70°C |
Bending radius min. | min. 10 x D |
Loop resistance | max. 73.2 Ω/km |
Capacitane
Capacity imbalance |
nom. 100 nF/km
300 pF/100 m |
Insulation resistance min. | min. 100 MΩ x km |
Test voltage | 800 V |
Operating voltage max. | 300 V |
Standards | DIN VDE 0815 |
Fire performance | Vertical flame propagation EN 60332-1-2
Corrosive gas EN 60754-1/2 Smoke density EN 61034-2 |
EU declaration of conformity | LVD Low Voltage Directive 2014/35/EU
RoHS Restriction of Hazardous Substances 2011/65/EU |
Used in smart building systems as an EIB instabus communication cable. The cable is protected against ambient electromagnetic interference by its static screen. Used in KNX-compatible home and building electronic systems (HBES) providing automated central or remote control of fixed interior installations for heating, cooling and ventilation in dry or wet areas, lighting, motorised curtains and blinds, audio, video, CCTV, fire detection, security and intercom installations.
Conductor Electrolytic copper wire
Insulation HFFR, in compliance with DIN VDE 0815 insulation colour coding 70°C EN 50290-2-26
Screen Pet tape min. 100% coverage Tinned copper drain wire Al-Pet tape min. 100% coverage
Sheath HFFR – RAL6018 Green 70°C, EN 50290-2-27