PROFIBUS FC

Category:
Temperature range -20°C …+70°C
Bending radius min. min. 15 x D
Loop resistance max. 110 Ω/km
Screen resistance nom. 9 Ω/km
Insulation resistance

Capacitance

Rated impedance

Velocity of propagation

min. 5000 MΩ x m

nom. 28.5 pF/m

150 ± 15 Ω

78%

Test voltage 1500 V
Operating voltage max.

Attenuation

Max 300 V

@20°C max. 9.6 kHz 0.30 dB/100 m 38.4 kHz 0.40 dB/100 m 4 MHz 2.20 dB/100 m 16 MHz 4.20 dB/100 m

Standards IEC 61158, EN 50170
Fire performance Vertical flame propagation EN 60332-1-2 (PVC-LSZH) Corrosive gas EN 60754-1/2 (LSZH) Smoke density EN 61034-2 (LSZH)
EU declaration of conformity LVD Low Voltage Directive 2014/35/EU RoHS Restriction of Hazardous Substances 2011/65/EU

Efficient high-speed data transmission in industrial automation applications. Easy-to-install and cost-effective thanks to the master/slave connection over a single bus cable. IEEE 802.3:10Base-T; 100Base-T; 1000Base-T IEEE 802.5 16 MB; ISDN; TPDDI; ATM Power over Ethernet (PoE) / PoE+

Conductor Electrolytic copper wire, Ø 22AWG Insulation Physical foam PE, Ø 2.55 mm, a(N) wire – green / b(P) wire – red 70°C, EN 50290-2-23 Inner sheath PVC – Natural, Ø 5.50 mm LSZH/LS0H – Natural, Ø 5.50 mm Screen Al-Pet foil min. 100% coverage Tinned braided copper wire, 85% coverage Sheath PVC – RAL 4001 Purple, Ø 8.0 mm TM51 70°C, EN 50290-2-22 LSZH/LS0H – RAL4001 Purple, Ø 8.0 mm 70°C, EN 50290-2-27