Temperature range | fixed -30°C …+70°C
flexing 0°C …+50°C |
Bending radius min. | fixed min. 7.5 x D
flexing min. 15 x D |
Conductor resistance | 0.22 mm2 max. 96.0 Ω/km
0.50 mm2 max. 39.0 Ω/km 0.75 mm2 max. 26.0 Ω/km 1.0 mm2 max. 19.5 Ω/km 1.5 mm2 max. 13.3 Ω/km 2.5 mm2 max. 7.98 Ω/km |
Insulation resistance min. | min. 200 MΩ x km |
Test voltage | 0.22 mm2 1200 V
0.50 mm2 1200 V 0.75 mm2 1200 V 1.0 mm2 1200 V 1.5 mm2 2500 V 2.5 mm2 2500 V |
Operating voltage max. | max. 300 V |
Standards | TSE K 353, DIN VDE 0812 |
Fire performance | Vertical flame propagation EN 60332-1-2
Corrosive gas EN 60754-1/2 Smoke density EN 61034-2 |
EU declaration of conformity | LVD Low Voltage Directive 2014/35/EU
RoHS Restriction of Hazardous Substances 2011/65/EU |
Halogen-free insulated and sheathed, twisted-pair cable range is used for signal transmission in interior installations. Flexible and slim design provides installation advantages in confined spaces. Used in industrial electronics, computers and office equipment, indoor communication, audio and security systems. Cables are composed of halogen-free materials (flame retardant materials that do not emit toxic gas or black dense smoke that lowers visibility). They are primarily used in highly populated areas that should have fire resistance.
Conductor Stranded copper wire Class 5, IEC 60228
Insulation HFFR, in compliance with DIN 47100 vinsulation colour coding 70°C EN 50290-2-26, HJ2 DIN VDE 0207-23
Strand Pairs are bundled together in stranded layers
Separator Polyester tape min. 100% coverage
Sheath HFFR, RAL 7001 Grey 70°C EN 50290-2-27, HM2 DIN VDE 0207-24