LIH(St)CH

Temperature range fixed -30°C …+70°C

flexing 0°C …+50°C

Bending radius min. fixed min. 7.5 x D

flexing min. 15 x D

Conductor resistance 0.22 mm2 max. 96.0 Ω/km

0.50 mm2 max. 39.0 Ω/km

0.75 mm2 max. 26.0 Ω/km

1.0 mm2 max. 19.5 Ω/km

1.5 mm2 max. 13.3 Ω/km

2.5 mm2 max. 7.98 Ω/km

Insulation resistance min. min. 200 MΩ x km
Test voltage 0.22 mm2 1200 V

0.50 mm2 1200 V

0.75 mm2 1200 V

1.0 mm2 1200 V

1.5 mm2 2500 V

2.5 mm2 2500 V

Operating voltage max. max. 300 V
Standards TSE K 353, DIN VDE 0812
Fire performance Vertical flame propagation EN 60332-1-2

Corrosive gas EN 60754-1/2

Smoke density EN 61034-2

EU declaration of conformity Low Voltage Directive 2014/35/EU

RoHS Restriction of Hazardous Substances 2011/65/EU

Halogen-free insulated and sheathed range is used for signal transmission in interior installations. Flexible and slim design provides installation advantages in confined spaces. Used in industrial electronics, computers and office equipment, indoor communication, audio and security systems. The cable is protected against ambient electromagnetic interference by its foil and braided screen. Cables are composed of halogen-free materials (flame retardant materials that do not emit toxic gas or black dense smoke that lowers visibility). They are primarily used in highly populated areas that should have fire resistance. Upon demand, following customized types with numeric codes can be manufactured. LIH(St)CH-OZ: black core with white number codes LIH(St)CH-JZ: black core with white number codes, ground protection conductor (yellow/green)

Conductor Stranded copper wire Class 5, IEC 60228

Insulation HFFR, in compliance with DIN 47100 insulation colour coding 70°C EN 50290-2-26, HJ2 DIN VDE 0207-23 Screen Al-Pet tape min. 100% coverage Tinned braided copper wire

Sheath HFFR, RAL 7001 Grey 70°C EN 50290-2-27, HM2 DIN VDE 0207-24